Install Step of GRP Water Tank

Preparation before installation


1.Foundation production

  • Foundation type: Design a concrete foundation or steel frame platform according to the size and shape of the water tank.
  • Load-bearing requirements: The foundation must be able to withstand the weight of the water tank when fully loaded (water weight + tank weight).
  • Flatness: The horizontal error of the foundation surface is ≤3mm to avoid deformation of the tank due to uneven force.
  • Drainage design: Drainage ditches are reserved around the foundation to prevent water accumulation from corroding the bottom of the tank.

2.Check materials and tools

  • Check whether the water tank module, bolts, sealant (such as neutral silicone), rubber gasket and other accessories are complete.
  • Prepare tools: level, wrench, screwdriver, cleaning cloth, etc.

Water tank assembly steps


1.Bottom plate installation

  • Put the bottom plate module flat on the foundation according to the drawing, align the joints, and use bolts to fix it initially.
  • Use a level to check the flatness of the bottom plate, adjust it to be completely horizontal, and tighten the bolts.

2.Installation of side panels and partitions

  • Sequence: Splice from the bottom layer to the top layer, and each layer of side panels needs to be installed with staggered seams (avoid through seams).
  • Sealing treatment:
  • Rubber sealing strips are embedded in the joints of the panels, and sealant is applied on the outside (thickness is about 2-3mm).
  • Bolts need to be tightened evenly diagonally to prevent local stress concentration.

3.Top panel installation

  • The top panel module covers the top of the side panel, and the joint treatment is the same as the side panel.
  • Reserve the position of the inspection hole (manhole) to ensure that the opening size is consistent with the design.

Installation of key accessories


1.Pipeline connection

  • Inlet and outlet pipes: flange connection, lined with rubber gaskets, check for leakage after tightening the bolts.
  • Overflow pipe and sewage pipe: The overflow pipe mouth should be 5-10cm lower than the top of the water tank, and the slope of the sewage pipe should be ≥2% to facilitate drainage.
  • Valves and instruments: Install water level gauges, valves, etc. for daily monitoring.

2.Safety accessories

  • Install escalators and guardrails (1.2m above the top of the water tank), and lock the manhole cover to prevent foreign objects from entering.
  • Lightning rods must be installed on outdoor water tanks, and the grounding resistance must be ≤10Ω.

Sealing test

1.Full water test

  • Fill water to the designed water level, let it stand for 24 hours, and observe whether the joints and pipe connections are leaking.
  • If leakage is found, drain the water and reapply sealant or adjust the tightness of the bolts.

2.Air pressure test (optional)

  • Introduce 0.05MPa compressed air into the closed water tank, maintain pressure for 30 minutes, and the pressure drop is ≤10% to be qualified.

Environment and safety measures


Spacing requirements: reserve ≥0.8m maintenance passages around the water tank, and leave ≥0.5m space on the top.

Insulation and antifreeze: In cold areas, insulation materials (such as polyurethane foam) must be covered, and heating belts are activated when the water temperature is below 0℃.

Anti-pollution measures: Regularly clean and disinfect the inner wall of the water tank, and install insect-proof nets on the vents.

Acceptance and maintenance


1.Acceptance standards

  • Sealing, verticality (deviation ≤1‰), water quality testing.

2.Daily maintenance

  • Clean once every six months, check the aging of the sealant, and replace it in time.
  • Drain idle water tanks in winter to prevent freezing and cracking.

3.Precautions

  • Prohibited operations: Welding and knocking on the tank to avoid damaging the fiberglass layer.
  • Professional construction: It is recommended that large water tanks (≥50m³) be installed under the guidance of the manufacturer to avoid structural errors.
  • Emergency treatment: If cracks appear on the tank, stop using it immediately and contact the manufacturer for repair.